Short Circuit Test of Transformer

It is a method in electrical engineering used to determine the copper or winding loss and also it determines the impedance of the transformer . The circuit diagram of this is shown below. In this, the secondary winding (low voltage side is shorted by a thick conductor) and on primary side(high voltage side) Ammeter(A), Voltmeter(V) and wattmeter(W) are connected.

Transformer

so, generally short circuit test is performed on high winding side and short circuited on low winding side. It will read copper losses because of high current passing through windings.

we have Power losses ( W s. c) = I2 s. c * Re

Hence, Re = W s c / I2s.c

we know that, Impedance( Z e ) = Vs .c / Is. c

Reactance(X e ) = sqrt((impedance)2 – (resistance)2 )

Example:

A short circuit test is conducted on a transformer and noted the following recordings V s .c = 7V , Is .c = 1.5mA , W s .c = 4W, Calculate the Reactance(X e ) , resistance(Re ) ?

Solution:

Given that, V s. c = 7V , I s. c = 1.5mA , W s . c = 4W

now, resistance ( Re ) = W s. c / I2 s. c

so, Resistance (Re ) = 1.8Ω

Impedance(Z e ) = V s .c / I s. c => 7/1.5

Now, Reactance( X e ) = sqrt((impedance)2 – (resistance)2 )

X e = 1.46Ω

Open and Short Circuit Test of Transformer

In this article, we will go through the Open and Short circuit tests of a Transformer. Open and short circuit tests are performed on a Transformer to evaluate its performance characteristics and parameters which mainly determine the Voltage regulation of the transformer, the Transformer’s efficiency, and the Equivalent circuit of the Transformer. They determine Iron and copper losses in the transformer. In this tutorial, we will go through the open and short circuit tests on a transformer with their circuit diagrams and an example and also we will tabulate the differences between the two.

Similar Reads

Basic Terminologies

Short circuit: An electrical connection in which current flows along a path that has very little resistance. This may result in high current flow, damage to the equipment, heating, etc., Open circuit: It is an electrical connection in which there is a break in the path in which electric current flows. This may result in High resistance, no current flow, etc., Transformer: An electrical device that is used to transfer electrical energy from one circuit to another without physical connection through electromagnetic induction.Now, let us learn open circuit tests and short circuit tests step by step with an example for each....

Open Circuit Test of Transformer

It is a method in electrical engineering used to determine the iron or core loss and it determines the exciting current of the transformer when it operates at rated voltage. The circuit diagram of this is shown below. In this, the secondary winding or the high voltage side is left open and the low voltage side is used to perform the test completely. Using this test we calculate no-load circuit parameters(X0, R0) and iron loss....

Short Circuit Test of Transformer

It is a method in electrical engineering used to determine the copper or winding loss and also it determines the impedance of the transformer . The circuit diagram of this is shown below. In this, the secondary winding (low voltage side is shorted by a thick conductor) and on primary side(high voltage side) Ammeter(A), Voltmeter(V) and wattmeter(W) are connected....

Differences Between Open Circuit Test and Short Circuit Test

OPEN CIRCUIT TEST SHORT – CIRCUIT TEST also known as no – load test also known as Impedance test main aim is to calculate the iron loss and exciting current of the transformer main aim is to calculate the copper or winding loss and the impedance of the transformer primary winding is connected to rated voltage source primary winding is connected to low- voltage source secondary winding is open – circuited secondary winding is short – circuited voltmeter is connected across the primary winding to measure the applied voltage voltmeter is connected across secondary winding to measure secondary voltage ammeter is connected in series with the primary winding to measure primary current ammeter is connected in series with primary winding to measure short – circuit current...

Conclusion

Both the open circuit test and short circuit test are done to measure the efficiency of the transformer through various parameters in each case, voltage regulation. In this article, we have covered this topic in detail. We have covered Open CIrcuit Test and Short Circuit Test both separately with proper example....

Contact Us